Skip to content
ICS / SCADA

Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 Series Power Meter — Default Password

Default username and password for the Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 Series Power Meter: user1 / pass1. Learn how to log in and how to change the default credentials.

Schneider Electric PowerLogic PM5500/PM5600/PM5700 are panel-mount power meters used in building management, industrial power monitoring, and utility metering. The web interface ships with two default user accounts. For older firmware (PM5560/PM5562/PM5563/PM5580 firmware 2.9.9 or earlier; PM5570/PM5660/PM5760 firmware 3.2.9 or earlier), user1/pass1 has web-master (full access) and user2/pass2 has product-master (limited) privileges. Newer firmware (4.0.0+ or 6.0.0+) replaces the static defaults with username Administrator and the device MAC address (uppercase, no colons) as the password. Display passcode defaults to 0000. Default credential change is required at commissioning.

Nom d’utilisateurMot de passeAccèsVersion / firmwareNotes
user1
pass1
Web UIFirmware ≤2.9.9 (PM5560/PM5562/PM5563/PM5580); ≤3.2.9 (PM5570/PM5660/PM5760)Web master account — full configuration access.
user2
pass2
Web UIFirmware ≤2.9.9 (PM5560/PM5562/PM5563/PM5580); ≤3.2.9 (PM5570/PM5660/PM5760)Product master account — read and limited configuration access.

Utilisation responsable

Cette base de données répertorie les identifiants par défaut documentés publiquement afin que les administrateurs puissent les trouver et les changer. Utilisez-les uniquement sur des systèmes que vous possédez ou que vous êtes autorisé à tester.

Appareils associés